Additional Info:
"Features
1-channel isolated barrier
24 V DC supply (Power Rail)
TC, RTD, potentiometer or voltage input
Current output 0/4 mA ... 20 mA
Sink or source mode
Configurable by PACTwareTM
Line fault (LFD) and sensor burnout detection
Up to SIL2 acc. to IEC 61508

Function
This isolated barrier is used for intrinsic safety applications. It is designed to
connect RTDs, thermocouples, or potentiometers in the hazardous area, and
provide a proportional 0/4 mA ... 20 mA signal to the safe area.
The barrier offers 3-port isolation between input, output, and power supply.
A removable terminal block K-CJC-** is available for thermocouples when internal
cold junction compensation is desired.
A fault is indicated by a red flashing LED per NAMUR NE44 and user-configured fault
outputs.
The unit is easily programmed with the PACTwareTM configuration software.
A collective error messaging feature is available when used with the Power Rail
system.
"

Buyers' Review